hohner |
Hohner Automation Ltd. |
Home | Distributors | Terms | About Us | Accessories | Download 3D AutoCAD |
Series MXE stainless steel (Exd) tachometer with 4 ... 20 mA output |
|
M | E | K | 5 | - | 0 | 5 | X | X | - | X | X | X | X | |||||||||||
| |
|
|___| |
| |
| |
|
Speed (RPM) |
|||||||||||||||||||
| | | |
Connection |
| | 4mA = 0 RPM | |||||||||||||||||||||
| | | | 1 = 2m cable | | | 20mA = Max RPM | |||||||||||||||||||||
|
| | Shaft | 3 = 10m cable | | | Rated RPM: | ||||||||||||||||||||
| | K5 = 12 x 20 mm |
| |
Min 300 |
||||||||||||||||||||||
Protection |
Exit |
Max 3000 | |||||||||||||||||||||||
E = IP66/X7 |
A = Axial | ||||||||||||||||||||||||
St. Steel |
R = Radial | ||||||||||||||||||||||||
Class I, Zone 1; Zone 21; Class II, Div 2 |
Technical Data | Connection Options | ||||
Operating temp: | - 20 ...+ 60 degrees C |
9412 |
Cable |
||
- 4 ...+ 140 degrees F |
+ Loop |
1 | Red | ||
Weight: | 43 oz (1.2 kg) |
- Loop |
2 | Black | |
Protection: | IP 65/X7 | ||||
Housing: | Stainless Steel | ||||
Shaft: | Stainless Steel | ||||
Bearings: | Ball Races 2 x 6001 ZZ | ||||
Torque: |
0.7 oz/in (5 N-cm) |
Output |
|||
Humidity: |
Up to 98% permissible |
*4...20mA span based on 250 ohm load |
|||
Max Speed: |
3000 RPM max. |
||||
Shaft load: |
Supports its own weight |
||||
Precision: |
|||||
0 rpm = +/- 0.05mA |
|||||
1 rpm to max rpm = +/- 0.2 mA |
Certifications |
Flameproof, does not require barrier for use in hazardous areas, and we use a barrier gland for added safety |
IP 66/X7 |
ATEX [Certificate] |
IECEx [Certificate] |
CSA [Certificate] |
GOST-CU [Certificate] |
Mounting Instructions |
Hook up the encoder with the connections as described. Make sure power supply meets specifications. Attach encoder to mounting bracket as shown. Attach shaft using a flexible coupling. |
Dimensions |
|
Hohner Automation Ltd. | Tel: +44 (0) 1978 363-888 |
Whitegate Industrial Estate | Fax: +44 (0) 1978 364-586 |
Wrexham LL13 8UG | E-mail: uksales@hohner.com |