hohner |
Hohner Automation Ltd. |
Home | Distributors | Terms | About Us | Accessories | Download 3D AutoCAD |
Series IP3000 incremental heavy duty shaft encoder up to 12 mm |
|
3 | X | K | 1 | - | 1 | 3 | X | X | - | X | X | X | X | ||||||||||
| |
Shaft Size |
| |
| |
Resolution - ppr |
||||||||||||||||||||
| |
12 x 25 mm |
| |
Exit |
|||||||||||||||||||||
| |
|
| |
A = Axial |
|||||||||||||||||||||
Housing Type |
| |
R = Radial |
||||||||||||||||||||||
D = Stainless Steel |
Connection |
|||||||||||||||||||||||
|
1 = 2m cable |
|||||||||||||||||||||||
2 = 5m cable |
||||||||||||||||||||||||
3 = 10 m cable |
||||||||||||||||||||||||
|
H = 9512 12 pin plug & socket |
|||||||||||||||||||||||
5...24 Volt Extended Line Driver is standard, optional Current Sink Open Collector is available
IECEx
Zone 0, Class 1 Div 1 |
Technical Data | Connection Options | |||
Operating temp: | - 20 ...+ 60 degrees C | Cable | ||
- 4 ...+ 140 degrees F | PS GND | Black | ||
On request: | -20 ... + 100 degrees C | PS 5 ... 24 V | Red | |
Max frequency: | 150 kHz | Output A | White | |
Current consumption: | 50 mA (max.) | Output B | Blue | |
Power supply: | 5 - 24V | Output O | Yellow | |
Weight: | 125 oz (3.5 kg) SS | Output A inv | Green | |
Output B inv | Violet | |||
Protection: | IP 66/X7 | Output O inv | Brown | |
Housing: | Stainless Steel | |||
Shaft: | Stainless Steel | Output | ||
Bearings: | 2 x 6001 - (Z) (RS) | Diagram is shown with clockwise shaft rotation viewed from | ||
Torque: | 0.7 oz/in (5 N-cm) | shaft end | ||
Humidity: | Up to 98% permissible | |||
Speed: | 6000 RPM max. | |||
Shock: | 10g (6msec) | |||
Vibration: | 5g (500 Hz) | |||
Shaft load: | Radial / Axial 10 N | |||
Line driver output max: | 50 mA per channel | |||
Max. ppr: | 5000 | |||
Inertia: | 30 gm-cm2 |
Certifications |
To use the encoder in a hazardous area, a safety barrier or galvanic isolator has to be used. Our six channel barrier and isolator work with our encoders. Isolator Data Sheet |
IP 66/X7 |
ATEX [Certificate] |
IECEx [Certificate] |
CSA [Certificate] |
GOST-CU [Certificate] |
Mounting Instructions |
Hook up the encoder with the connections as described. Make sure power supply meets specifications. Attach encoder to mounting bracket as shown. Attach shaft using a flexible coupling. |
Dimensions |
|
Hohner Automation Ltd. | Tel: +44 (0) 1978 363-888 |
Whitegate Industrial Estate | Fax: +44 (0) 1978 364-586 |
Wrexham LL13 8UG | E-mail: uksales@hohner.com |
United Kingdom | Web: www.hohneronline.co.uk |